7 kW at 230 V, power factor 1 works out at 30.43 A: 7 kW × 1,000 ÷ (230 V × 1) = 30.43 A.

What to convert

Between 0.01 and 1,000,000

Supply

Leave empty for the standard. WA is 240 V single phase and 415 V three phase.

Between 100 and 480. For 12, 24 or 48 V, use the battery tools

12, 24 or 48 V? Use the battery runtime calculator

Power factor

Leave empty for 1 (heaters, kettles) or 0.8 for kVA (generators).

Power factor is at most 1 (and at least 0.1)

See result ↓

Your result

Result

30.43 A

7 kW × 1,000 ÷ (230 V × 1) = 30.43 A

You typed
7 kW at 230 V, power factor 1
Apparent power (kVA)
7
Power factor used
1

Fix the highlighted field to update.

Link copiedShared

Power point checkOver a 15 A power point's rating. Loads like this are usually hardwired on their own circuit. Ask a licensed electrician. An estimate, not electrical advice.

How we calculated this

  • Multiply the volts by the power factor. Amps are the watts divided by that.
  • On three phase, the volts are also multiplied by the square root of three before dividing.
  • kW is kVA times power factor. An empty voltage means the standard at the meter.

Full method, tables and sources: Watts to amps calculator

  1. Check the inputs

    7 kW at 230 V, power factor 1

  2. Use the formula

    7 kW × 1,000 ÷ (230 V × 1) = 30.43 A

This version starts with a 7 kW load on single phase, like an EV wall charger. Type your kW, or switch to three phase.

kW to amps: what to know

Official source

  • 1 kW draws 4.35 A at 230 V single phase and 1.44 A per phase at 400 V three phase. Schneider Electric's Electrical Installation Guide gives 4.35 A and 1.44 A.
  • An induction cooktop such as the Westinghouse WHI633BC is rated 6,500 W: about 28.26 A at 230 V. Its maker lists it as a hardwired appliance. Ask a licensed electrician.

Estimate

  • A 7 kW EV wall charger draws about 30.43 A at 230 V. Our own figure for a wall charger is 32 A at 230 V, which is 7.36 kW. Ask a licensed electrician.
kW to amps at 230 V, 240 V and 400 V three phase
kW230 V single phase240 V (WA)400 V three phase
14.35 A4.17 A1.44 A per phase
1.56.52 A6.25 A2.17 A per phase
28.70 A8.33 A2.89 A per phase
2.410.43 A10.00 A3.46 A per phase
313.04 A12.50 A4.33 A per phase
3.615.65 A15.00 A5.20 A per phase
521.74 A20.83 A7.22 A per phase
730.43 A29.17 A10.10 A per phase
7.532.61 A31.25 A10.83 A per phase
1043.48 A41.67 A14.43 A per phase
1565.22 A62.50 A21.65 A per phase
2295.65 A91.67 A31.75 A per phase
  • A standard power point is rated 10 A and the larger one 15 A, and everything on the same power point or power board shares that rating. In the 230 V single phase column, 2 kW draws 8.70 A, 3 kW draws 13.04 A and 3.6 kW draws 15.65 A. From 3.6 kW up the rows are more than either is rated for: loads like that are usually hardwired on their own circuit. Ask a licensed electrician.
  • For the same kW, single phase draws 3.01 times the amps of each phase on 400 V three phase: 7 kW is 30.43 A at 230 V and 10.10 A per phase at 400 V.
  • In WA, where the standard is 240 V, 7 kW draws 29.17 A: 1.26 A less than at 230 V.

Every cell is the calculator on this page, run for that row at power factor 1, the figure for a heater or kettle (Estimate). 230 V and 400 V are the standard at the meter in the eastern states and 240 V is the standard in WA (Official source). A standard power point is rated 10 A (Dated third-party source) and the larger one 15 A (Official source). Sources: Wikipedia, AS/NZS 3112: a standard socket-outlet is 230 V at a maximum of 10 A; WorkSafe Victoria safety alert (27 Mar 2012): 15 amp plug tops do not fit 10 amp socket-outlets (read via the Wayback Machine). An estimate, not electrical advice. Ask a licensed electrician.

Before you type a kW figure

An air conditioner's kW is not the kW it draws

The median 7.1 kW split on the Energy Rating registry has a rated cooling input of 2 kW, and the median 14 kW ducted system 4.18 kW.

Source: Energy Rating registry ac_2026_09_17.csv (data.gov.au), medians of deduplicated available models (Official source). Checked 1 October 2026.

The size in an air conditioner's name is the heat it moves, so type the rated input here, not the size. At power factor 1, the calculator's default, a rated input of 2 kW is 8.70 A at 230 V and 4.18 kW is 18.17 A. Both are amps at the rated input, not the most a unit can draw: our data holds no figure for that, and no power factor for an air conditioner. So neither figure says what power point or circuit a unit needs. Ask a licensed electrician. Typed as 7.1 kW, the split would read 30.87 A. What those sizes cost to run: the air conditioner running cost calculator.

For power points, power factor and 230 or 240 V, see the main watts to amps calculator.