How long will a 100Ah battery last?

By Last reviewed

Runtime = usable Wh ÷ watts drawn from the battery. A 100 Ah LiFePO4 battery (1,024 Wh usable) runs an 80 W TV through a small inverter for 10.8 hours, not the 15 hours a simple Ah × volts ÷ watts sum gives.

Your battery and load

LiFePO4 is 12.8 V a block.

Between 1 and 2,000

From the appliance's rating plate.

Between 1 and 20,000

A 230 V appliance needs an inverter.

Inverter

Maker figures. Continuous watts at 25 °C in brackets.

No model for this voltage. Pick another, or type both figures.

Maker's peak figure.

Between 50 and 100

What it uses switched on with no load.

Between 0 and 200

Advanced settings
Advanced

If the maker gives Wh. Replaces Ah × volts.

Between 10 and 100,000

Depth of discharge you allow.

Between 10 and 100

Lead-acid loses Ah at high current. 1 turns it off.

Between 1 and 1.5

Continuous discharge from your battery's spec.

Between 1 and 2,000

See result ↓

Your result

Runtime

10.8 hours

1,024 Wh usable ÷ 94.9 W at the battery = 10.8 h

Usable energy
1,024Wh
At the battery
94.9W
Battery current
7.4A
C-rate
0.07C
Without idle draw
11.5h
Common shortcut
15h

The shortcut: volts × Ah ÷ watts, all of the battery, no inverter. It is what many tools show.

Choosing an inverter? Check its size and the current it pulls.

Fix the highlighted field to update.

Link copiedShared

How we calculated this

  1. Usable energy

    Wh = nominal volts × Ah × the share you can use. LiFePO4 is 12.8 V a 12 V block (4 cells of 3.2 V), lead-acid 12 V. Lead-acid also loses capacity at high current (step 4).

    12.8 V × 100 Ah × 80% = 1,024 Wh

  2. Power at the battery

    A 230 V load goes through an inverter: load ÷ efficiency, plus the inverter's own idle draw. The idle draw runs as long as the inverter is on, even with nothing plugged in. A DC load is rated at the system voltage, the way fridge makers give Ah an hour at 12 V. It draws watts ÷ system volts in amps from any battery, so its runtime is usable Ah ÷ those amps.

    80 W ÷ 90% + 6 W idle = 94.9 W

  3. Runtime

    Hours = usable Wh ÷ watts at the battery.

    1,024 Wh ÷ 94.9 W = 10.8 h

  4. Current and rate effect

    Current = watts at the battery ÷ volts. For lead-acid we cut the capacity with Peukert's rule: rated Ah × (Ah ÷ (current × 20 h)) ^ (exponent − 1), never above the rated Ah. LiFePO4 holds its capacity up to 1C, so it gets no cut.

    7.4 A, 0.07C, 100% of rated capacity

Your load on each battery type
BatteryUsable WhHours
LiFePO4 (lithium)1,02410.8
Lead-acid (AGM, gel or flooded)5355.6
Shortcut: volts × Ah, all of it, no inverter1,20015

Each type at its default usable share and rate effect, same capacity, load and inverter. The shortcut row is what you get from volts × Ah ÷ watts.

Battery defaults
TypeNominalUsable sharePeukertCurrent limit
LiFePO412.8 V (Official source)80% (Official source)1 (Estimate)1C (Official source)
Lead-acid12 V (Official source)50% (Official source)1.25 (Official source)No source

Victron battery monitors default to a Peukert exponent of 1.25 for lead-acid, and Victron calls it "no more than a rough approximation": at very high current the battery gives even less. Constant-power loads like an inverter lose capacity faster still.

Victron AGM and GEL: capacity by discharge time
Discharge timeAGMGEL
20 h100%100%
10 h92%87%
5 h85%80%
3 h78%73%
1 h65%61%
30 min55%51%

Measured at a constant current (Official source: Victron GEL and AGM datasheet). Our Peukert figure of 1.25 is a little more cautious than this table for AGM.

Inverter figures (Victron datasheets)
InverterContinuous 25 / 40 °CPeakBatteryPeak efficiencyIdle draw
Victron Phoenix 250 VA (200 W)200 / 175 W400 W12 / 24 / 48 V87% / 88% / 88%4.2 W / 5.2 W / 7.9 W
Victron Phoenix 375 VA (300 W)300 / 260 W700 W12 / 24 / 48 V89% / 89% / 90%5.6 W / 6.1 W / 8.5 W
Victron Phoenix 500 VA (400 W)400 / 350 W900 W12 / 24 / 48 V90% / 90% / 91%6 W / 6.5 W / 9 W
Victron Phoenix 800 VA (650 W)650 / 560 W1,500 W12 / 24 / 48 V90% / 90% / 91%6.5 W / 7 W / 9.5 W
Victron Phoenix 1200 VA (1,000 W)1,000 / 850 W2,200 W12 / 24 / 48 V91% / 91% / 92%10 W / 11 W / 12 W
Victron Phoenix 1600 VA (1,450 W, 12 V)1,450 / 1,200 W2,200 W12 V92%12 W
Victron MultiPlus-II 3000 VA (2,400 W)2,400 / 2,200 W5,500 W12 / 24 / 48 V93% / 94% / 95%13 W / 13 W / 11 W
Victron MultiPlus-II 5000 VA (4,000 W)4,000 / 3,700 W9,000 W12 / 24 / 48 V95% / 96% / 96%15 W / 18 W / 18 W
Victron MultiPlus-II 8000 VA (6,400 W, 48 V)6,400 / 5,500 W15,000 W48 V95%29 W
Victron MultiPlus-II 10000 VA (8,000 W, 48 V)8,000 / 7,000 W18,000 W48 V96%38 W
Victron MultiPlus-II 15000 VA (12,000 W, 48 V)12,000 / 10,000 W27,000 W48 V95%55 W

Efficiency curve not published; we use the maker's peak efficiency plus its no-load draw, which is our estimate. Victron reaches its peak at part load, so a full load does a little worse. Model names are in VA: a 1200 VA Phoenix gives 1,000 W.

100 Ah LiFePO4 current limits (maker spec pages)
BatteryDischarge limitStatus
Victron LFP Smart 12,8/100200 A continuous; 1C (100 A) or less recommendedOfficial source
Renogy 12.8 V 100 Ah100 A continuous; 300 A for 5 secondsOfficial source
Enerdrive B-TEC 100 Ah G2100 A for 30 minutes at 25 °COfficial source

With no limit typed, we warn above 1C (Victron's recommended continuous discharge). Always use your own battery's figure. We do not size cables or fuses: use the maker's installation manual, and a licensed electrician for anything on 230 V.

“Official source” means read in full on the maker’s own datasheet, manual or spec page, or in an official dataset (BOM). “Dated third-party source” means read on a dated third-party page, such as a product test. “Not yet checked” means one non-official source. “Estimate” means our own pick or reasoning: type your own figure.

Sources

The one formula

Runtime in hours = usable watt hours ÷ watts drawn from the battery.

  • Usable Wh = nominal volts × amp hours × the share you can use. A 12.8 V, 100 Ah LiFePO4 battery holds 1,280 Wh. At 80% usable that is 1,024 Wh.
  • Watts at the battery: a DC appliance is rated at the system voltage (a 12 V fridge in Ah an hour at 12 V), so it draws watts ÷ system volts (12, 24 or 48 V) in amps from any battery. Its runtime is usable Ah ÷ those amps. For a 230 V appliance it is the load ÷ the inverter’s efficiency, plus the inverter’s own idle draw.

Three things most calculators leave out

  1. The inverter’s idle draw. An inverter uses power as soon as it is on. Victron’s Phoenix 500 VA uses 6 W on 12 V with nothing plugged in. The Phoenix 1200 VA uses 10 W, which is 240 Wh a day. On a small load that is a big share.
  2. The usable share. Victron battery monitors use 50% as the default floor for lead-acid. Two lithium makers rate their cycle life at 80% depth of discharge. Using 100% of either is not realistic.
  3. Lead-acid at high current. Victron AGM batteries give 85% of their rated capacity over 5 hours and 65% over 1 hour. We use Peukert’s rule with Victron’s default exponent of 1.25 to cut the capacity as the current rises.

Voltage: 12 V or 12.8 V

A LiFePO4 battery is four 3.2 V cells, so it is 12.8 V nominal, not 12 V. A lead-acid battery is six 2 V cells, 12 V. For 24 V and 48 V systems the figures double and quadruple. More volts means less current for the same watts, which matters for the next point.

The current check

Current = watts at the battery ÷ volts. Batteries have a continuous current limit. Renogy and Enerdrive limit their 100 Ah LiFePO4 batteries to 100 A. Victron allows 200 A on its 100 Ah model but recommends 1C (100 A) or less because of heat. A 2,000 W kettle through an inverter pulls about 174 A from a 12.8 V battery at 90% efficiency. The calculator warns you when you pass the limit.

What this calculator does not do

  • It does not size cables or fuses. Use the battery and inverter maker’s installation manual, and a licensed electrician for anything on 230 V.
  • It uses one efficiency figure. Makers publish their peak efficiency and their idle draw, not a curve, so a full load does a little worse than shown.
  • It assumes a battery at room temperature. Victron says its LiFePO4 batteries hold 80% of their capacity at 0 °C.

Questions

How do I work out how long a battery will last?

Usable Wh ÷ watts at the battery. Usable Wh is volts × Ah × the share you can use (about 80% for LiFePO4, 50% for lead-acid). Watts at the battery is the load ÷ inverter efficiency, plus the inverter’s idle draw.

Why is my answer shorter than other calculators?

Most skip the inverter’s losses and its own idle draw (4 to 15 W for Victron’s 12 V models, all day), and they use all of the battery. Lead-acid also gives less than its rated Ah at high current. The common shortcut in the result shows the gap.

Does an inverter use power with nothing plugged in?

Yes. Victron’s Phoenix 1200 VA draws 10 W on 12 V with no load. That is 240 Wh a day, about 19 Ah from a 12.8 V battery. Switch it off, or use its ECO mode, when you do not need 230 V.

Is a LiFePO4 battery 12 V or 12.8 V?

12.8 V nominal: four 3.2 V cells (Victron). A 100 Ah LiFePO4 battery holds 1,280 Wh, not 1,200 Wh.

What is the Peukert effect?

A lead-acid battery gives fewer Ah when you draw a high current. Victron AGM batteries give 85% of their rated capacity over 5 hours and 65% over 1 hour. LiFePO4 barely changes up to 1C.

How much current can my battery supply?

Read your battery’s spec. Renogy and Enerdrive limit their 100 Ah LiFePO4 batteries to 100 A (Enerdrive for 30 minutes). Victron recommends 1C or less. Type your limit under Advanced settings.