Watts to amps calculator (Australia, 230 V)

By Last reviewed

At Australia's standard 230 V, amps = watts ÷ 230. So 1,000 W draws about 4.35 A, and 2,400 W about 10.43 A. A heater or kettle labelled 2,400 W draws less at 230 V, about 9.58 A: the watts on its label are for 240 V. A standard 10 A power point is rated for about 2,300 W at 230 V (2,400 W at 240 V, which is why power boards say 10 A / 2,400 W). On 400 V three phase, 11 kW is about 15.88 A per phase.

What to convert

Between 0.01 and 1,000,000

Supply

Leave empty for the standard. WA is 240 V single phase and 415 V three phase.

Between 100 and 480. For 12, 24 or 48 V, use the battery tools

12, 24 or 48 V? Use the battery runtime calculator

Power factor

Leave empty for 1 (heaters, kettles) or 0.8 for kVA (generators).

Power factor is at most 1 (and at least 0.1)

See result ↓

Your result

Result

10.43 A

2,400 W ÷ (230 V × 1) = 10.43 A

You typed
2,400 W at 230 V, power factor 1
Apparent power (kVA)
2.4
Power factor used
1

Fix the highlighted field to update.

Link copiedShared

Power point check2,400 W ÷ 230 V is 10.43 A, over a standard 10 A power point's rating. That sum reads high for a heater or kettle: the watts on its label are for 240 V, and at 230 V the same element draws about 9.58 A. A 15 A power point (larger earth pin) is rated for 15 A. A 15 A plug will not fit a 10 A socket, on purpose. An estimate, not electrical advice.

How we calculated this

  1. Check the inputs

    An empty voltage means the standard at the meter: 230 V single phase, 400 V three phase. On three phase the voltage is line to line and the amps are per phase. kVA to kW and kW to kVA use no voltage, only the power factor.

    2,400 W at 230 V, power factor 1

  2. Use the formula

    Amps = watts ÷ (volts × power factor). Three phase adds √3 under the line. kW = kVA × power factor.

    2,400 W ÷ (230 V × 1) = 10.43 A

Common appliances on single phase at power factor 1 (your voltage, or 230 V for kVA to kW and kW to kVA)
ApplianceWattsAmpsSource
Kettle (rated 220 to 240 V: the watts are at the top of that range)2,400 W10.43 AOfficial source: Breville BKE425 the Soft Top Dual: 2400 Watts, 220 - 240 Volts
Oil column heater2,400 W10.43 ADated third-party source: CHOICE electric heater lab tests, updated 27 May 2026
Fan heater2,000 W8.70 ADated third-party source: CHOICE electric heater lab tests, updated 27 May 2026
Panel heater2,200 W9.57 ADated third-party source: CHOICE electric heater lab tests, updated 27 May 2026
Clothes dryer (vented, 5 kg)1,750 W7.61 AOfficial source: Fisher & Paykel vented dryer user guide (DE5060M): Rated Power (W) 1750, 220 to 240 V
Split system (3.5 kW, cooling)870 W3.78 AOfficial source: Energy Rating registry median rated cooling input, 185 models
Induction cooktop (60 cm)6,500 WHardwired, own circuitOfficial source: Westinghouse WHI633BC 60 cm induction cooktop (hardwired)
EV wall charger7,360 WHardwired, own circuitEstimate: Worked out as 230 V × 32 A, single phase

Amps are the watts in the row ÷ the voltage. For a heater or kettle that reads a little high at 230 V: the watts on its label are for 240 V.

Typical power factors (Schneider Electric)
LoadPower factor
Heater, kettle, oven element1
Induction motor at 0% load0.17
Induction motor at 25% load0.55
Induction motor at 50% load0.73
Induction motor at 75% load0.8
Induction motor at 100% load0.85
Fluorescent light, uncompensated0.5
Fluorescent light, compensated0.93
Every figure this calculator uses
ValueFigureStatusSource
Standard voltage, single phase230 VOfficial sourceESC Electricity Distribution Code of Practice v3.1 (1 Jan 2026), Table 1, p.86: "230 V Meter"
Standard voltage, three phase400 VOfficial sourceESC Electricity Distribution Code of Practice v3.1 (1 Jan 2026), Table 1, p.86: "400 V Meter"
WA voltage240 V and 415 VOfficial sourceWestern Australian Service and Installation Requirements (April 2023), p.41: 240 volt single-phase (+/- 6%)
Range at the meter in Victoria216 to 253 VOfficial sourceESC Electricity Distribution Code of Practice v3.1 (1 Jan 2026), Table 2 notes (from AS 61000.3.100)
What homes measure240 to 245 V in Qld, NSW and VicOfficial sourceUNSW CEEM, Voltage Analysis of the LV Distribution Network in the Australian NEM, report for the ESB (May 2020): average in Qld (p.59), median in NSW and Vic (pp.69, 82)
Standard power point10 ADated third-party sourceWikipedia, AS/NZS 3112: a standard socket-outlet is 230 V at a maximum of 10 A
Larger power point15 AOfficial sourceWorkSafe Victoria safety alert (27 Mar 2012): 15 amp plug tops do not fit 10 amp socket-outlets (read via the Wayback Machine)
Power board label10 A / 2,400 WOfficial sourceNT WorkSafe, safe use of power boards: "maximum capacity of 10 Amps/2400 Watts" (read via the Wayback Machine)
Power factor, watts and amps1EstimateOur choice: resistance heating is cos φ = 1 (Schneider Electric Electrical Installation Guide, read via the Wayback Machine)
Power factor, kVA and kW0.8EstimateOur choice: large generator sets are rated at 0.8 PF under ISO 8528 (Caterpillar / FG Wilson and Kohler spec sheets)

Sources

Questions

Is Australia 230 V or 240 V?

The standard at the meter is 230 V in the eastern states. Victoria's Electricity Distribution Code of Practice gives a range of 216 to 253 V at the meter. Many homes measure 240 to 245 V in Qld, NSW and Vic (UNSW, 2020). WA is still 240 V. At the same watts, 240 V gives about 4% fewer amps than 230 V. Type your own voltage if you know it.

Why does my heater's label give a voltage range?

The watts on the label are for the top of the range, 240 V. A heater or kettle element is close to a fixed resistance. So a 2,400 W heater rated at 240 V draws about 9.58 A and 2,204 W at 230 V. The calculator divides the watts you type by the voltage, so for 2,400 W it shows 10.43 A. That is a little high for a heater with that label, which errs on the cautious side.

How many watts can a 10 A power point take?

About 2,300 W at 230 V and 2,400 W at 240 V. That is why power boards are labelled 10 A / 2,400 W (NT WorkSafe). Everything on one power point or power board shares that 10 A.

Can I plug a 15 A appliance into a 10 A power point?

No. A 15 A plug has a larger earth pin, so it will not fit a 10 A socket, on purpose (WorkSafe Victoria). Ask a licensed electrician to fit a 15 A power point.

Can I run a heater from a power board?

Plug heaters and other high-current appliances straight into the wall. A board shares one 10 A power point between everything on it. Do not use piggyback adaptors (Energy Safe Victoria), and do not join boards together (NT WorkSafe).

What about motors, pumps and fridges starting?

They draw several times more for a moment when they start: about 7.5 times the running current for a motor started direct on line (Schneider Electric). The calculator shows the running current only.

What is power factor?

Real power (kW) ÷ apparent power (kVA). A heater is 1. An induction motor is 0.85 at full load and 0.17 with no load (Schneider Electric). Large generators are rated at 0.8, so kVA equals kW only for heaters and kettles.

On three phase, is it 400 V or 230 V?

Both. 400 V is between two phases (line to line). Each phase to neutral is 230.94 V (400 ÷ √3). Use 400 V here, and the amps are per phase. WA is 415 V.

What size circuit breaker do I need?

We do not give breaker sizes. Only blogs publish typical values, and your wiring decides. A load over a power point rating is usually hardwired on its own circuit. Ask a licensed electrician.